Seitenansicht 38
Coding Field
Selection or range
Factory setting (bold)
Display Info
P8
Enter upper alarm
threshold
16.00 pH
-2.00 ... 16.00 pH
Omitted when P5 = Off.
P9
Select process
monitoring
(PCS alarm)
Off
AC
CC
AC+CC
AC!
CC!
ACCC!
AC = Sensor alternation check,
CC = Controller check.
Alarm signalling optionally with or
without simultaneous controller
switch-off.
xxxxx = without controller
switch-off,
xxxx! = with controller switch-off.
P10
Enter maximum
permissible
period for lower
alarm threshold
60 min
0 ... 2000 min
Only when P9 = CC or AC+CC.
P11
Enter maximum
permissible
period for upper
alarm threshold
120 min
0 ... 2000 min
Only when P9 = CC or AC+CC.
P12
Enter alarm
threshold
(for P10 / P11)
1.00 pH
-2.00 ... 16.00 pH
Selected value is an absolute
value. This function is mainly
used for batch process and
single-sided limit switches.
Factory settings are printed in bold face;
base version does not include functions in
italic
.
P8
pH
HighAlarm
16.00
P9
ProcMonit
Off
P10
min
Tmax Low
60
P11
min
Tmax High
120
P12
pH
Setpoint
1.0
PM253E5A.CHP
Liquisys M CPM 223 / 253 Instrument configuration
Endress+Hauser 37